Firmware upgrading (98.70)
new features of "i.75.98.70"
- Support mDNS.
- Provide a new parameter(CTCratio).
- provide reactive power and kvarh in modbus/tcp.
mDNS
The mDNS protocol is supported since this version.
Before: if you do not know the IP of the device,the user can only use the SSDP discovery like "How to find the the meter already connected to your router" or log in to the router to find the IP that is allocated.
Now :the energy meter can be accessed by this URL(http://sn.local) , like the below pic.
New parameter(CTCratio)
You want to monitor a balanced output with two high legs and one neutral line, but there is only phase C left now (Phase A and phase B are already used to monitor the grid of 120/240V or 120/208V).
This parameter of "CTCratio" will help you solve this problem. If it is set to '2', the energy meter`s reading of current, active power reading, and Kwh will be doubled in phase C.
Because it is a balanced output. Measure one high leg and doubling its reading would be nearly the same result as measure two high legs and sum them together.
For more details ,please refer to Monitor the system of 120/240V or 120/208V in North America
No. | API | Description |
---|---|---|
1 | /api/ctcratio | inquiry the reading of ctcratio |
2 | /api/ctcratio?x=2 | set the CTCratio to 2 |
3 | /api/ctcratio?x=1 | set the CTCratio to 1 |
Set the CTCratio to 2
/api/ctcratio?x=2
Query the setting of the CTCratio
/api/ctcratio
Different result of Phase C in different CTCratio
Add reactive power and kvarh in modbus/tcp
The register map of the modubs/tcp is updated as below.
index | Register address(Dec) | Register address(Hex) | register len | Description |
---|---|---|---|---|
1 | 0 | 0000 | 1 | Phase A voltage,unsigned,value=data/100,unit: V |
2 | 1 | 0001 | 1 | Phase A current,unsigned,value=data/100,unit: A |
3 | 2 | 0002 | 2 | Phase A active power,signed,value=data,unit: W |
4 | 4 | 0004 | 2 | Phase A forward energy,unsigned,value=data/800,unit:kWh |
5 | 6 | 0006 | 2 | Phase A reverse energy,unsigned,value=data/800,unit:kWh |
6 | 8 | 0008 | 1 | Phase A power factor,unsigned,value=data/1000 |
7 | 9 | 0009 | 1 | model: 1:WEM3080 2:WEM3080T 3:WEM3046T 4:WEM3050T |
8 | 10 | 000A | 1 | Phase B voltage,unsigned,value=data/100,unit: V |
9 | 11 | 000B | 1 | Phase B current,unsigned,value=data/100,unit: A |
10 | 12 | 000C | 2 | Phase B active power,signed,value=data,unit: W |
11 | 14 | 000E | 2 | Phase B forward energy,unsigned,value=data/800,unit:kWh |
12 | 16 | 0010 | 2 | Phase B reverse energy,unsigned,value=data/800,unit:kWh |
13 | 18 | 0012 | 1 | Phase B power factor,unsigned,value=data/1000 |
14 | 19 | 0013 | 1 | PadB 0x00,not used |
15 | 20 | 0014 | 1 | Phase C voltage,unsigned,value=data/100,unit: V |
16 | 21 | 0015 | 1 | Phase C current,unsigned,value=data/100,unit: A |
17 | 22 | 0016 | 2 | Phase C active power,signed,value=data,unit: W |
18 | 24 | 0018 | 2 | Phase C forward energy,unsigned,value=data/800,unit:kWh |
19 | 26 | 001A | 2 | Phase C reverse energy,unsigned,value=data/800,unit:kWh |
20 | 28 | 001C | 1 | Phase C power factor,unsigned,value=data/1000 |
21 | 29 | 001D | 1 | PadC 0x00,not used |
22 | 30 | 001E | 1 | frequency, unsigned,value=data/100,unit:Hz |
23 | 31 | 001F | 1 | padH 0x00,not used |
24 | 32 | 0020 | 2 | sum of power,signed,value=data,unit:W |
25 | 34 | 0022 | 2 | sum of forward energy,unsigned, value=data/800, unit:kWh |
26 | 36 | 0024 | 2 | sum of reverse energy,unsigned, value=data/800, unit:kwh |
27 | 38 | 0026 | 2 | Phase A reactive power, signed,value=data,unit: var |
28 | 40 | 0028 | 2 | Phase A Inductive reactive energy, unsigned,data/1000,unit: kvarh |
29 | 42 | 002A | 2 | Phase A capacitive reactive energy, unsigned,data/1000,unit: kvarh |
27 | 44 | 002C | 2 | Phase B reactive power, signed,value=data,unit: var |
28 | 46 | 002E | 2 | Phase B Inductive reactive energy, unsigned,data/1000,unit: kvarh |
29 | 48 | 0030 | 2 | Phase B capacitive reactive energy, unsigned,data/1000,unit: kvarh |
27 | 50 | 0032 | 2 | Phase C reactive power, signed,value=data,unit: var |
28 | 52 | 0034 | 2 | Phase C Inductive reactive energy, unsigned,data/1000,unit: kvarh |
29 | 54 | 0036 | 2 | Phase C capacitive reactive energy, unsigned,data/1000,unit: kvarh |
30 | 56 | 0038 | 8 | serial number of the device |
test the modbus/tcp function by a software